Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2010 | ELECTRIC - FINAL | Partial Approval | ||
| 10/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1- MISSING COVER FOR MAIN BREAKER AT SERVICE 2-SERVICE NOT GROUNDED PER CODE 2 GROUND RODS 6-MIN APART 3- SUB PANEL NOT LABELED WHICH FEEDER IS FOR UNIT 4 4- INSTALL APPROVED GROUND BAR IN SUB PANEL ALSO HOW DOES SUB PANEL GET POWER |