Permit: T10EL02455

Parcel: 135040930


Addresses:

1834 S AVENIDA URSA

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/02/2010 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) ONLY POWER SERVICE DROP CONDUCTORS CAN BE ATTACHED TO SERVICE MAST., COAX LINE FROM CABLE COMPANY CANNOT BE ATTACHED TO SERVICE MAST. NEC 230.28