Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ONLY ONE CONDUCTOR PER LUG |
|
| 11/01/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL UNUSED OPENING IN BOTTOM OF SERVICE PANEL 2) FINISH #3 (NEED ADDRESSES FOR SERVICES) AND #5 BOND JUMPER FOR FEEDER RACEWAY |
|
| 10/25/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHERE DRYWALL HAS BEEN ADDED BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 2) BATHROOM RECEPT TO BE GFCI PROTECTED 3) IDENTIFY AND LABEL SERVICES 4) USE APPROVED CONNECTORS FOR NM CABLE AT NEW SUB PANEL 5) USE CORRECT SIZED BONDING JUMPER |