Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2010 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 11/09/2010 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY DERATING OF CONDUCTOR 310.15 2) PANEL LABELING TO BE PER 408.3 3) IDENTIFY GROUNDED CONDUCTOR AT WEATHER HEAD 4) WHERE IS GROUNDING ELECTRODE SYSTEM AT 2ND STRUCTURE ? 5) WHERE ARE GAS AND WATER BONDS 6) NEED DISCONNECTING MEANS 2ND STRUCTURE 225.30,31,32 APPLY |