Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T10EL02360

Parcel: 11942006L

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
REPLACEMENT PARTS ARE LISTED AS AN ASSEMBLY DUE TO DETERIORATED CONDITIONS IT IS RECOMMENDED TO INSTALL CATALOG #020-509-01-00-0 IN THIS PEDESTAL
10/29/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/27/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/26/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) METER PEDESTAL IS NOT NEW OR REPLACED-IT HAD BEEN REBUILT AND MODIFIED. THERE ARE DETERIORATED PARTS STILL INTERNALLY-A THIRD PARTY NRTL INSPECTION IS NEEDED. THIS INSPECTOR IS NOT QUALIFIED TO RE-CERTIFY EQUIPMENT
2) WHERE IS MAIN BONDING JUMPER 250.24
3) SHEET METAL THREADS NOT ALLOWED FOR GROUNDING 250.12
4) NO HOOK UP TO TRAILER AT THIS TIME