Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10EL02360

Parcel: 11942006L

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL02360

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
REPLACEMENT PARTS ARE LISTED AS AN ASSEMBLY DUE TO DETERIORATED CONDITIONS IT IS RECOMMENDED TO INSTALL CATALOG #020-509-01-00-0 IN THIS PEDESTAL
10/29/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/27/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/26/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) METER PEDESTAL IS NOT NEW OR REPLACED-IT HAD BEEN REBUILT AND MODIFIED. THERE ARE DETERIORATED PARTS STILL INTERNALLY-A THIRD PARTY NRTL INSPECTION IS NEEDED. THIS INSPECTOR IS NOT QUALIFIED TO RE-CERTIFY EQUIPMENT
2) WHERE IS MAIN BONDING JUMPER 250.24
3) SHEET METAL THREADS NOT ALLOWED FOR GROUNDING 250.12
4) NO HOOK UP TO TRAILER AT THIS TIME