Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL02360
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* REPLACEMENT PARTS ARE LISTED AS AN ASSEMBLY DUE TO DETERIORATED CONDITIONS IT IS RECOMMENDED TO INSTALL CATALOG #020-509-01-00-0 IN THIS PEDESTAL |
|
10/29/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/27/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) METER PEDESTAL IS NOT NEW OR REPLACED-IT HAD BEEN REBUILT AND MODIFIED. THERE ARE DETERIORATED PARTS STILL INTERNALLY-A THIRD PARTY NRTL INSPECTION IS NEEDED. THIS INSPECTOR IS NOT QUALIFIED TO RE-CERTIFY EQUIPMENT 2) WHERE IS MAIN BONDING JUMPER 250.24 3) SHEET METAL THREADS NOT ALLOWED FOR GROUNDING 250.12 4) NO HOOK UP TO TRAILER AT THIS TIME |