Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL02355
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/25/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/09/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WAITING ON LABEL PER 702.8 2) EATON IS GOING TO RE-LABEL EQUIPMENT 3) OK TRANSFORMER 3 4) OK PANEL LABELING |
|
05/03/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* MEET WITH CONTRACTOR TO DISCESS TAP RULES & BUSWAY MARKING |
|
05/02/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) TAP RULES APPLY FOR TRANSFORM 3 2) BUSE WAYS ARE MARKED 277/480 V - BEING FED 120/208 3) PANEL SCHEPULES TO BE PER 408.4 4) IS GENERATOR BEING INSTALLED UNDER 700 OR 701 OR 702? 5) PROVIDE LABELING PER THE .8 SECTION OF THE SPPROIATE CODE |