Permit: T10EL02355

Parcel: 11615088L

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL02355

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/25/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/09/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) WAITING ON LABEL PER 702.8
2) EATON IS GOING TO RE-LABEL EQUIPMENT
3) OK TRANSFORMER 3
4) OK PANEL LABELING
05/03/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
MEET WITH CONTRACTOR TO DISCESS TAP RULES & BUSWAY MARKING
05/02/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) TAP RULES APPLY FOR TRANSFORM 3
2) BUSE WAYS ARE MARKED 277/480 V - BEING FED 120/208
3) PANEL SCHEPULES TO BE PER 408.4
4) IS GENERATOR BEING INSTALLED UNDER 700 OR 701 OR 702?
5) PROVIDE LABELING PER THE .8 SECTION OF THE SPPROIATE CODE