Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2010 | ELECTRIC - RECONNECT | Approved | ||
| 09/29/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED LICENSED ELECTRICIAN TO EVALUATE AND CORRECT AS NEEDED, THE ENTIRE DISTRIBUTION SYSTEM FOR THE PROPERTY, AND PROVIDE A WRITTEN REPORT ON SAME ON THE COMPANY LETTER HEAD-IN PARTICULAR HOUSE SUB PANEL IN KITCHEN, WHICH HAS 3 OR 4 CIRCUITS TIED INTO 1 BREAKER, DISTRIBUTION TO N.W. OUT BLDG, 3 PRONG OUTLETS ON 2 WIRE LINES, ETC... 2) VERIFY AND ADDRESS PERMITS FOR CARPORT, N.W. OUT BLDG, NORTH PORCH 3) INSTALL GFI IN KITCHEN COUNTER OUTLETS 4) INSTALL SMOKE DETECTORS IN BEDROOMS AND OUTSIDE BEDROOMS 5) ONE CANNOT GO THRU A BEDROOM TO GET TO ANOTHER BEDROOM, ADDRESS THIS WITH FLOOR PLAQN AT DEVELOPMENT SERVICES |