Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BONDING JUMPER TO BOND BUSHING OFF SET NIPPLE 2) MARK "SERVICE DISCONNECT" 3) SEAL OPENING AT WIRE ENTRY BACK OF PANEL WITH NON COMBUSTIBLE MATERIAL |
|
| 09/30/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS 2) OK WATER BOND 3) RECALL FOR BRANCH CIRCUITS WHEN READY 4) LINE SIDE INSPECTION ONLY |