Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* LOWER LEVEL: 1) ROMEX EXPOSED IN CEILING AREA 2) PROVIDE SWITCH AND PLUG COVERS 3) PLUG OPEN HOLES IN ELECTRIC BOXES 4) LIGHT FIXTURES BROKEN, BARE WIRES EXPOSED 5) WIRES NUTTED WITHOUT JUNCTION BOXES UPPER LEVEL: 1) PROVIDE PROTECTIVE GLOBE AT PORCH LIGHT 2) REFER TO RECONNECT REQUIREMENTS AND MAKE ALL CORRECTIONS PRIOR TO NEXT INSPECTION 3) LIGHT ABOVE SINK NOT WIRED TO CODE 4) REPLACE BROKEN OUTLETS 5) YOU MUST PROVIDE A MEANS OF HEAT TO A MINIMUM OF 68 DEGREES PRIOR TO OCCUPANCY, RECONNECT WILL NOT BE GIVEN, THIS ENTIRE UNIT IS FED BY A #12 AND THIRTY AMP BREAKER. PROVIDE CORRECT WIRING AND AMPLE POWER SUPPLY |