Permit: T10EL02199

Parcel: 132111400

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/23/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/21/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1 THRU 3 DATED 9/23/10 NOT CORRECTED
2) FURNACE NOT PROPERLY INSTALLED, LIFE SAFETY HAZARD
3) PROVIDE BLANKS AT PANEL DEAD FRONT
4) WH/FURNACE FLUE TO BE 10' AWAY OR 3' ABOVE COOLER INLET
5) THIS IS AN UNGROUNDED SYSTEM, REMOVE ALL GROUNDED OUTLETS AND REPLACE WITH NON GROUNDED OUTLETS
6) PROVIDE GLOBES ON INTERIOR LIGHT FIXTURES
7) PROVIDE OUTLET COVER PLATES
8) ALL CORRECTIONS WILL BE MADE PRIOR TO NEXT INSPECTION OR RE-FEE'S WILL BE ADDED
09/23/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE GLOBES AT LIGHT FIXTURES
2) ALL EXPOSED WIRING TO BE IN CONDUIT THIS INCLUDES ROMEX
3) PANELS NOT LABELED
4) KEY DOES NOT WORK IN DOOR NO INTERIOR INSPECTION MADE AT THIS TIME
5) PLEASE REFER TO RECONNECT GUIDE LINES AS PROVIDE BY CITY OF TUCSON