Permit: T10EL02190

Parcel: 112062500


Addresses:

2110 E COPPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/30/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/23/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DRYWALL SCREWS NOT APPROVED FOR RISER CONDUIT SUPPORT, USE MINIMUM 1/4" HARDWARE, 2 X 4 SUPPORT TO WALL ?
2) LOAD CONDUCTORS NOT TO PASS THRU SHIELDED AREA OR TOP-SEE LISTING NOTES
3) SUPPORT OR STRAP # BAR TO WALL
4) TERMINATE #10 CONDUCTORS IN PANEL. SERVICE RE-ENERGIZED PRIOR TO INSPECTORS APPROVAL