Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/23/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRYWALL SCREWS NOT APPROVED FOR RISER CONDUIT SUPPORT, USE MINIMUM 1/4" HARDWARE, 2 X 4 SUPPORT TO WALL ? 2) LOAD CONDUCTORS NOT TO PASS THRU SHIELDED AREA OR TOP-SEE LISTING NOTES 3) SUPPORT OR STRAP # BAR TO WALL 4) TERMINATE #10 CONDUCTORS IN PANEL. SERVICE RE-ENERGIZED PRIOR TO INSPECTORS APPROVAL |