Permit: T10EL02109

Parcel: 138050440

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/17/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
11/03/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE #1,2 & 3 OF PREVIOUS INSPECTION
09/28/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CONDUCTORS TO BE IN RACEWAY THRU WALL
2) CABLES TO ENTER PANEL WITH 1/4" OF SHEATHING MINIMUM
3) FILL UNUSED PORTION OF OPENING WITH A NON COMBUSTIBLE PRODUCT
4) RECALL FOR 9/29/10
5) NEED STRAP BELOW ROOF LINE