Permit: T10EL02103

Parcel: 13204007A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL02103

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/22/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ENGINEER NEEDS TO APPEAL TO FIRE CODES ADMINISTRATOR AND BLDG OFFICIAL FOR #2,3 & 4 PREVIOUS INSPECTION
2) 400 AMP FUSES DO NOT MEET INTENT OF CODE 695.4 (B) (1)
09/14/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) ENTRANCE AT TOP OF CONTOLLER TO BE FOR WET LOCATION NFPA 20/10.1
2) PLEASE VERIFY FUSES AT SERVICE PER 695.4 (B) (1)
3) PLEASE VERIFY CONDUCTOR SIZES ON PLANS PER 695.6 (C) (D) 1 & 2
4) PER DAVE MANN NFPA 20/9.7 FOR JUNCTION BOXES DUE TO THE NATURE OF THE INSTALLATION AND ENTRANCE OF WATER TO EQUIPMENT
09/13/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FIRE PUMP PIPE RUN AND CONDUCTORS ONLY OK
2) NEED TO SEE TEST RESULTS ON SYSTEM ON FINAL