Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL02103
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/22/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ENGINEER NEEDS TO APPEAL TO FIRE CODES ADMINISTRATOR AND BLDG OFFICIAL FOR #2,3 & 4 PREVIOUS INSPECTION 2) 400 AMP FUSES DO NOT MEET INTENT OF CODE 695.4 (B) (1) |
|
| 09/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ENTRANCE AT TOP OF CONTOLLER TO BE FOR WET LOCATION NFPA 20/10.1 2) PLEASE VERIFY FUSES AT SERVICE PER 695.4 (B) (1) 3) PLEASE VERIFY CONDUCTOR SIZES ON PLANS PER 695.6 (C) (D) 1 & 2 4) PER DAVE MANN NFPA 20/9.7 FOR JUNCTION BOXES DUE TO THE NATURE OF THE INSTALLATION AND ENTRANCE OF WATER TO EQUIPMENT |
|
| 09/13/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FIRE PUMP PIPE RUN AND CONDUCTORS ONLY OK 2) NEED TO SEE TEST RESULTS ON SYSTEM ON FINAL |