Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CONTRACTORS SCOPE OF WORK COMPLETE 2) NOTE: FOR COMBO PERMIT RESOLVED TO HAVE POWER CLEARED |
|
| 09/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND UPPER JUNCTION BOX 2) BOX OVER FILLED 3) CORRECTLY IDENTIFY CONDUCTORS 4) FINISH #2 PREVIOUS INSPECTION 5) CALL FOR RECONNECT PERMIT #T10EL01563 BEFORE POWER RELEASED 6) LOCK HOLDS & NOTICES FOR COMBO PERMIT 7) CONDUCTORS IN RACEWAY TO BE COLOR FULL LENGTH 8) NEXT INSPECTION IF NOT COMPLETE WILL RESULT IN A REFEE |
|
| 09/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE POST ADDRESS FOR BLDG 2) CANNOT USE OLD PANEL AS JUNCTION BOX 3) VERIFY CONDUCTOR DERATING 310.15 & 310.16 4) USE APPROVED STRAPS FOR RISER 5) NEED ACCESS TO JUNCTION BOX AT EAVES 6) NUMEROUS OTHER VIOLATIONS. HAVE ELECTRICAL CONTRACTOR FIX PROBLEMS AND COMPLETE BEFORE NEXT INSPECTION. A REFEE MAY BE ASSESED FOR UN-NECESSARY INSPECTIONS |
|
| 09/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO WORK DONE-WILL NOT MAKE PUNCH LIST FOR ELECTRICIAN |