Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/16/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE UNCOVER GROUNDING TO INSPECT 2) OLD PANEL CANNOT BE USED AS A JUNCTION BOX 3) SUPPORT FOR RISER NOT TO BE IN JUST PLYWOOD 4) USE JOIST PER INSTRUCTIONS |