Permit: T10EL01981

Parcel: 126171610

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/30/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/26/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
2) CANNOT HAVE BREAKER POSITIONS HIGHER THAN 6'-7" NEC 240.24
3) REMOVE PAINT AT GROUND CLAMP CONNECTIONS TO PIPING SYSTEMS
4) SEAL OPENING AT WIRE ENTRY WITH NON-COMBUSTIBLE MATERIAL. THIS IS FOR ENTRY AT BACK OF PANEL
5) SECURE BELL BOX TO BLDG SURFACE