Permit: T10EL01965

Parcel: 135074450

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T10EL01965

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
10/21/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) REPAIRS TO GROUNDING ELECTRODE SYSTEM IS OK
2) PLANS DO NOT SHOW ANY WORK BEYOND 400A DISCONNECT. ALL NEW WORK REQUIRES PLANS AND PERMITS. SERVICE WILL NOT BE RELEASED UNTIL ALL NEW WORK IS PERMITTED WITH PLANS AND INSPECTED
3) SERVICE IS OK
10/20/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXISTING GROUNDING ELECTRODE CONDUCTOR AND BONDING JUMPER TO GAS AND WATER PIPING HAS BEEN CUT AND STOLEN
2) EXISTING SYSTEM TO BE REPAIRED OR NEW GROUNDING ELECTRODE SYSTEM AND BONDING SYSTEM TO BE INSTALLED