Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 09/23/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 12) USE OUTDOOR FITTINGS AT LB ON PANEL AND AT LB AT EAVE 2) EVERYTHING ELSE HAS BEEN CORRECTED |
|
| 09/08/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED LISTED MAST BRACE FOR RISER SUPPORT 2) SECONDARY CIRCUIT CONDUIT FITITNGS TO BE FOR WET LOCATION 3) AN APPROVED JUNCTION BOX WILL BE NEEDED FOR INTERIOR 4) SECURE AND STRAP NM CABLES PER CODE 334.12 5) RECALL AFTER CROSSOVER |
|
| 08/31/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH #1,2 & 3-NO GAS OR WATER BOND 2) DRIVE GROUND RODS FLUSH WITH GRADE 3) NEED PERMANENT ADDRESS LABEL 4) USE CORRECT SIZED BREAKER FOR CONDUCTOR AMPACITY |