Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL01896
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2010 | ELECTRIC - FINAL | Partial Approval | 1) SEE REST OF SERVICES ON FINAL | |
08/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE HAS GROUNDING ELECTRODE, WATER AND GAS BONDING MISSING 2) 3 PANEL ON BACK WALL 1 HAS BREAKER BLANKS MISSING AND OPEN J-BOX 3) BY BACK DOOR LIGHT SWITCH HANGING OUT OF BOX 4) BY SOUTH SIDE DOOR J-BOX OPEN OUTLETS SWITCH OUT COVER PLATES 5) BACK ROOM INDUSTRIAL SWITCH AND COVER HANGING BY WIRES ONLY & OUTLETS HAVE BROKEN COVERS 6) EMT PIPE AND OUTLET HANGING FROM CEILING, FLEX AND WIRES HANGING FROM CEILING WITHOUT WIRE NUTS TO, IN MAIN FLOOR 7) HAVE QUALIFIED ELECTRICIAN GO THRU BLDG BEFORE CALLING FOR INSPECTION |