Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO OPENINGS ALLOWED IN DEAD FRONT OF SERVICE PANEL 2) FRONT COVER OF DISCONNECT FOR A/C MISSING-REPLACE 3) FUSE HOLDER OF A/C DISCONNECT HAS BEEN EXPOSED TO WEATHER AND IS CRACKED-REPLACE 4) SEAL TIGHT FITTINGS AT A/C LOOSE 5) EXTERIOR RECEPTS REQUIRE GFCI PROTECTION 6) WIRES DANGLING FROM VARIOUS CEILING J-BOXES, TUCK IN AND INSTALL COVER PLATES 7) ROMEX DANGLING FROM HOLE IN CEILING IN KITCHEN WHERE TRACK LIGHTING WAS REMOVED. PROVIDE J-BOXES AND TERMINATE WIRES PROPERLY 8) ALL BEDROOMS REQUIRE SMOKE DETECTORS. INSTALL PER MANUFACTURES INSTRUCTIONS 9) EAST BATHROOM REQUIRES GFCI RECPT ABOVE COUNTER 10) ALL RECEPTS ABOVE KITCHEN COUNTERS REQUIRE GFCI PROTECTION 11) REPLACE ANY CRACKED/BROKEN RECEPT PLATES 12) NUMEROUS VIOLATIONS IN GARAGE NEED TO BE CORRECTED OR REMOVED EXAMPLES: EXPOSED ROMEX, IMPROPER WIRING AND J-BOX METHODS 13) REMOVE 2-WIRE CONDUCTOR FROM HIGH RECEPT IN MASTER CLOSET IF CONNECTED TO POWER 14) B-VENTS FOR WATER HEATER AND FURNACE RQUIRE MINIMUM 1" CLEARANCE TO COMBUSTIBLES |