Permit: T10EL01893

Parcel: 141191160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/26/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/10/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO OPENINGS ALLOWED IN DEAD FRONT OF SERVICE PANEL
2) FRONT COVER OF DISCONNECT FOR A/C MISSING-REPLACE
3) FUSE HOLDER OF A/C DISCONNECT HAS BEEN EXPOSED TO WEATHER AND IS CRACKED-REPLACE
4) SEAL TIGHT FITTINGS AT A/C LOOSE
5) EXTERIOR RECEPTS REQUIRE GFCI PROTECTION
6) WIRES DANGLING FROM VARIOUS CEILING J-BOXES, TUCK IN AND INSTALL COVER PLATES
7) ROMEX DANGLING FROM HOLE IN CEILING IN KITCHEN WHERE TRACK LIGHTING WAS REMOVED. PROVIDE J-BOXES AND TERMINATE WIRES PROPERLY
8) ALL BEDROOMS REQUIRE SMOKE DETECTORS. INSTALL PER MANUFACTURES INSTRUCTIONS
9) EAST BATHROOM REQUIRES GFCI RECPT ABOVE COUNTER
10) ALL RECEPTS ABOVE KITCHEN COUNTERS REQUIRE GFCI PROTECTION
11) REPLACE ANY CRACKED/BROKEN RECEPT PLATES
12) NUMEROUS VIOLATIONS IN GARAGE NEED TO BE CORRECTED OR REMOVED EXAMPLES: EXPOSED ROMEX, IMPROPER WIRING AND J-BOX METHODS
13) REMOVE 2-WIRE CONDUCTOR FROM HIGH RECEPT IN MASTER CLOSET IF CONNECTED TO POWER
14) B-VENTS FOR WATER HEATER AND FURNACE RQUIRE MINIMUM 1" CLEARANCE TO COMBUSTIBLES