Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T10EL01857
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
11/22/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUB PANEL NOT WIRED PROPERLY, NEUTRALS AND EQUIPMENT GROUNDING CONDUCTORS TIED TOGETHER-NEED TO ISOLATE 2) NEUTRAL BEING USED AS UNGROUNDED CONDUCTOR- NEED TO GO THRU SUB PANEL 3) TIGHEN CONDUCTORS AS NEEDED |
|
11/15/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) NO KEY IN LOCK BOX |
|
10/21/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/04/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFI'S OUTLETS ON KITCHEN COUNTER, SWITCH AND OUTLET COVERS MISSING 2) ROMEX WIRES IN KITCHEN CEILING CANNOT BE HANGING DOWN 3' WITHOUT WIRE NUTS AND IN A BOX WITH A COVER 3) SHEETROCK MISSING ON STAIRWAY WALL EXPOSING J-BOX, NO STRAPPING AND HOW CAN YOU GET TO IT ONCE SHEETROCK IS PUT BACK AND LIGHT BOX BROKEN 4) BATHROOM ON 1ST FLOOR HAS EXHAUST FAN HANGING OUT OF WALL, SHEETROCK MISSING AND LIGHT SWITCH HANGING OUT OF WALL. OUTLET MISSING, WIRES EXPOSED, NO WIRE NUTS AND GFI'S MISSING 5) DOWNSTAIRS NO SMOKE DETECTORS, MISSING OUTLET COVER PLATES AND GFI'S NEEDED IN BATHROOM 6) TO MANY VIOLATIONS TO LIST, GET QUALIFIED ELECTRICIAN BEFORE CALLING IN ANOTHER INSPECTION |