Permit: T10EL01853

Parcel: 113103990


Addresses:

1622 E SPRING ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/06/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/05/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/04/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEUTRAL NOT BONDED PER CODE IN SERVICE PANEL, ALSO OVER HEATING AT NEUTRAL TERMINATION IN PANEL
2) INSTALL INSULATED BUSHING AND SEAL OPENING IN BACK OF PANEL WITH FIRE PROOFING CAULK OR OTHER APPROVED METHOD