Permit: T10EL01827

Parcel: 125122060


Addresses:

3413 E EDGEMONT ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/30/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/22/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL 2 GROUND RODS MINIMUM 6' APART
2) WATER BOND TO BE #4
3) GROUND RODS TO BE COMPLETELY DRIVEN AND CONDUCTOR TO BE STRAPPED/SECURED TO BLDG SERVICE
4) PANEL DIRECTORY
5) CHASE NIPPLE TO BE USED WITH LOCK NUT
6) CANNOT USE OLD DISCONNECT AS JUNCTION POINT
7) CONDUCTORS NOT SIZED PROPERLY FOR 20V AMP SERVICE
8) PROPERLY IDENIFY CONDUCTORS
9) BOND GAS PIPING