Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/22/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL 2 GROUND RODS MINIMUM 6' APART 2) WATER BOND TO BE #4 3) GROUND RODS TO BE COMPLETELY DRIVEN AND CONDUCTOR TO BE STRAPPED/SECURED TO BLDG SERVICE 4) PANEL DIRECTORY 5) CHASE NIPPLE TO BE USED WITH LOCK NUT 6) CANNOT USE OLD DISCONNECT AS JUNCTION POINT 7) CONDUCTORS NOT SIZED PROPERLY FOR 20V AMP SERVICE 8) PROPERLY IDENIFY CONDUCTORS 9) BOND GAS PIPING |