Permit: T10EL01802

Parcel: 12814144A


Addresses:

5283 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/11/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/09/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ITEMS AT SERVICE EQUIP. NOT CORRECTED YET, CANNOT SPLICE GROUNDING ELECTRODE CONDUCTOR WITH WIRE NUT; CONDUCT TERM. IN BACK OF PANEL HAS LOOSE LOCKNUT. NEED TO BE SURE GROUNDING ELECTRODE SYSTEM IS INTACT. PLEASE HAVE LICENSED OR QUALIFIED ELECTRICIAN TO MAKE REPAIRS OR CORRECTIONS TO AVOID RE-INSPECTION FEES. INSPECTION TERMINATED AT THIS POINT.
07/27/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ENTIRE ELECTRICAL SYSTEM IS IN DIS-REPAIR, HAVE OPEN BOXES, DAMAGED RACEWAYS, OPEN & DAMAGED PANELS/DISCONNECTS, EXPOSED CONDUCTORS, SERVICE PANEL IN DIS-REPAIR AND MISSING KNOCK OUTS
2) NO GROUND ELECTRODE SYSTEM
3) TO MANY ITEMS TO LIST
4) OBTAIN SERVICES OF ELECTRICAL CONTRACTOR TO GO THROUGH ENTIRE BLDG., INCLUDING ROOF, SERVICE AND SUB PANELS
5) MAKE CORRECTIONS TO HAZARDS THRU OUT BLDG
6) INSTALL GFI PROTECTION ON RECEPTS WHERE REQUIRED
7) NEED TO HAVE LADDER FOR ROOF ACCESS FOR NEXT INSPECTION