Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL01792
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2010 | ELECTRIC - FINAL | Approved | DRAWINGS FOR FIELD REVISIONS ACCEPTED AND APPROVED. | |
09/13/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/23/2010 | ELECTRIC - FINAL | Denied | 1) REVISE PLAN TO SHOW J-BOXES AND LIGHT FIXTURE REPLACEMENT 2) REMOVE EXISTING BALLASTS AND BOTTOM SUPPORTING LIGHT ARMS. 3) YOU MUST HAVE RED-LINES FOR USING "BONE-YARD" LIGHTS APPROVED BEFORE FINAL. |