Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED GFI PROTECTION FOR KITCHEN COUNTER AND BATH OUTLETS 2) NEED SMOKE DETECTORS IN BEDROOMS, AT LEAST 3' AWAY FROM A/C REGISTERS 3) OBTAIN PERMIT FOR, OR REMOVE SUN SHADE ON REAR PATIO 4) RECALL FOR ELECTRIC FINAL AFTER POWER IS RESTORED |