Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/26/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 2) GROUND RODS TO BE 6' MIN APART AND 8' INCONTACT WITH SOIL 3) USE APPROVED HARDWARE FOR DEVICE AND NEED ARC SHIELD |
|
| 07/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL NOT TO CODE MULTIPLE TERMINATIONS AT LUGS AND IMPROPER FITTINGS 2) PROTECT CONDUCTORS ENTERING PANEL AND SEAL UNUSED PORTION WITH NON COMBUSTIBLE 3) DETERIORATED CONDUCTOR TERMINATION AND IDENTIFY AS NEUTRAL 4) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG 5) VERIFY 2ND GROUND ROD AND PANEL LABELING 6) NEED HOLDOWN FOR MAIN BREAKER AND BREAKER LISTED BY MANUFACTURE 7) EXPOSED CABLE AND MISSING CONNECTOR AT HOOD 8) PLEASE VERIFY WIRING FOR "HOCKEY PUCK" LIGHTS IN KITCHEN ARCH |