Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/18/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUB PANEL HAS HOLES ON BOTTOM, 1 1/4 NEEDS STRAPPING 2) ROMEX WIRES MISSING RACEWAY 3) LB ON RIGHT SIDE LOOSE CONCENTRICS BROKE IN SUB PANEL AND MISSING DEAD FRONT 4) LABEL BREAKERS IN MAIN PANEL |
|
| 07/30/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BRANCH CIRCUITS ON FINAL PANEL SCHEDULE |
|
| 07/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE WIRES TO SAY SUN RESISTANT ON INSULATION 2) GROUNDING ELECTRODE TO BE STRAPPED TO WALL AND BONDED TO WATER AND GAS |