Permit: T10EL01745

Parcel: 123141020


Addresses:

845 E LINDEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T10EL01745

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2010 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
07/22/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) GROUNDING ELECTRODE CONDUCTOR NOT IN ?
2) ALSO PLEASE RE-GROUND WATER AND GAS PIPING
07/21/2010 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR HAS BEEN CUT, MAY NEED TO INSTALL 2 NEW GROUND RODS/#4 BARE
2) CABLE SHEATH NEEDS TO BE INSIDE PANEL 1/4"
3) EXPOSED WIRING AT STORE ROOM