Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/01/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED 2ND GROUND ROD FOR GROUNDING ELECTRODE SYSTEM 2) ONLY ONE CONDUCTOR PER LUG 3) PROVIDE SURFACE CONTACT FOR GROUND LUG NOT UNDER MOUTING SCREW 4) NEED PERMANENT METAL ADDRESS LABEL 5) SERVICE LOCATION IS AT FIRST INSPECTION |
|
| 07/20/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |