Permit: T10EL01742

Parcel: 138050960


Addresses:

750 W HATFIELD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/23/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED 2ND GROUND ROD FOR GROUNDING ELECTRODE SYSTEM
2) ONLY ONE CONDUCTOR PER LUG
3) PROVIDE SURFACE CONTACT FOR GROUND LUG NOT UNDER MOUTING SCREW
4) NEED PERMANENT METAL ADDRESS LABEL
5) SERVICE LOCATION IS AT FIRST INSPECTION
07/20/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*