| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) LINE SIDE INSPECTION ONLY 2) RECALL FOR BRANCH CIRCUITS AND GROUNDING WHEN READY |
|
| 08/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING SERVICE DISCONNECT 2) INSTALL MAIN BONDING JUMPER 3) PROPERLY EXTEND EQUIPMENT GROUNDS. SPLIT BOLT CONNECTIONS NOT USED PER INSTRUCTIONS OR LISTING 4) LABEL ALL BREAKERS 5) ALUMINUM AND COPPER CANNOT BE SPLICED TOGETHER 6) USE PROPER BREAKER SIZE FOR CONDUCTOR SIZE. 14 GAUGE TO BE ON 15A MAX 7) INSTALL 2 GROUND RODS, BOND GAS AND WATER PIPING |