Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL LISTED MAST BRACING 2) TIGHTEN GROUND CLAMP TO WATER PIPING 3) REMOVE PAINT UNDER GROUND CLAMP TO GAS PIPING 4) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG SURFACE 5) NEED PANEL DIRECTORY 6) EXPLAIN NEW BRANCH CIRCUITS 7) SEAL OPENING AT WIRE ENTRY ACK OF PANEL WITH NON COMBUSTIBLE MATERIAL 8) HAVE #10 EQUIPMENT GROUND ON ROMEX IN PANEL SPLICED AND CONTINUED WITH #12 |