Permit: T10EL01687

Parcel: 138041620

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/07/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
09/01/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) LOCKED, NO ACCESS AND DOGS IN YARD
08/30/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OUTDOOR RECEPTS COVER TO BE WEATHER PROOF WETHER OR NOT PLUGGED INTO 406.8
2) TIGHTEN LOOSE FITTINGS 3/4" CONDUIT ON SIDE ALSO STRAP CONDUIT PER CODE
3) USE CORRECT SIZED BREAKER AMPACITY FOR #8 NM CABLE 330.80
4) MISSING GROUNDED CONDUCTOR FOR 20 AMP CIRCUITS
08/17/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SECURE CABLE TO BACK OF BOX 312.5 (C)
2) RECALL NEXT WORKING DAY FOR LOAD CONNECTIONS
3) INCREASE RELEASED FOR LINE SIDE ONLY