Permit: T10EL01665

Parcel: 117090300


Addresses:

1037 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/23/2012 ELECTRIC - FINAL Approved
01/12/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) ONLY ONE CONDUCTOR PER LUG
2) FINISH PREVIOUS ITEMS 5 & 6
01/09/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONTRACTOR CHANGED SERVICE FROM RESIDENTIAL TYPE. ALL IN ONE TO COMMERCIAL METER BASE/DISC. SW. TO COMPLY WITH TEP REQUIREMENTS
2) INSTALL BOND BUSHING ON SUPPLY SIDE OF EQUIPMENT
3) CONDUCTORS SHOULD BE #2 CU FOR 100 AMP
4) INSULATING BUSHING REQUIRED FOR #4 AND LARGER
5) PERMIT IS FOR 200 AMP UPGRADE INSTALLED IS 100 AMP
6) USE APPROVED LISTED DEAD FRONT PER MANUFACTURER
12/29/2011 ELECTRIC - FINAL Denied SEAL KNOCKOUTS AT BOTH PANELS, INSTALL DEADFRONT, SECURE RECEPS IN OUTLET UNDER AWNING, PROPERLY INSTALL RECEP COVERS, SEE CORRECTION NOTES FROM 10/04/2011
10/04/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) RECEPTS IN FRONT CANOPY SHOULD BE GFI PROTECTED
2) LOOSE COVERS, BROKEN SECURITY LIGHT AND EXPOSED CONDUCTORS
3) CALL FOR FINAL AFTER LOADS CONNECTED
10/03/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/09/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CHECK SUB PANEL LATER
11/05/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) RISER TO USE LISTED MAST BRACE KIT
2) FINISH JUMPER TO 2ND GROUND ROD
3) NEED PERMANENT ADDRESS LABELING