Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2012 | ELECTRIC - FINAL | Approved | ||
| 01/12/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ONLY ONE CONDUCTOR PER LUG 2) FINISH PREVIOUS ITEMS 5 & 6 |
|
| 01/09/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONTRACTOR CHANGED SERVICE FROM RESIDENTIAL TYPE. ALL IN ONE TO COMMERCIAL METER BASE/DISC. SW. TO COMPLY WITH TEP REQUIREMENTS 2) INSTALL BOND BUSHING ON SUPPLY SIDE OF EQUIPMENT 3) CONDUCTORS SHOULD BE #2 CU FOR 100 AMP 4) INSULATING BUSHING REQUIRED FOR #4 AND LARGER 5) PERMIT IS FOR 200 AMP UPGRADE INSTALLED IS 100 AMP 6) USE APPROVED LISTED DEAD FRONT PER MANUFACTURER |
|
| 12/29/2011 | ELECTRIC - FINAL | Denied | SEAL KNOCKOUTS AT BOTH PANELS, INSTALL DEADFRONT, SECURE RECEPS IN OUTLET UNDER AWNING, PROPERLY INSTALL RECEP COVERS, SEE CORRECTION NOTES FROM 10/04/2011 | |
| 10/04/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RECEPTS IN FRONT CANOPY SHOULD BE GFI PROTECTED 2) LOOSE COVERS, BROKEN SECURITY LIGHT AND EXPOSED CONDUCTORS 3) CALL FOR FINAL AFTER LOADS CONNECTED |
|
| 10/03/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/09/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECK SUB PANEL LATER |
|
| 11/05/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RISER TO USE LISTED MAST BRACE KIT 2) FINISH JUMPER TO 2ND GROUND ROD 3) NEED PERMANENT ADDRESS LABELING |