Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/26/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/22/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #1,2,3 & 5 STILL ARE NOT TO CODE
07/14/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LB ON SIDE PANEL TO BE BONDED 250.90
2) LB'S TO HAVE WEATHER PROOF CONNECTORS AND SE CABLE MISSING RACEWAY TO PANEL
3) PERMIT TO INCLUDE A/C
4) SERVICE TO HAVE 2 GROUND RODS 6' APART
5) MISSING WATER AND GAS BOND