Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/22/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #1,2,3 & 5 STILL ARE NOT TO CODE |
|
| 07/14/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LB ON SIDE PANEL TO BE BONDED 250.90 2) LB'S TO HAVE WEATHER PROOF CONNECTORS AND SE CABLE MISSING RACEWAY TO PANEL 3) PERMIT TO INCLUDE A/C 4) SERVICE TO HAVE 2 GROUND RODS 6' APART 5) MISSING WATER AND GAS BOND |