Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) A PERMIT WILL BE NEEDED IN FUTURE FOR A/C |
|
| 07/15/2010 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/12/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) IDENTIFY ON UNINSULATED NEUTRAL 2) GENERAL LABELING NOT ALLOWED 408.4 3) PLEASE VERIFY PERMIT FOR NEW A/C UNIT 4) SEPERATE GROUNDS AND NEUTRAL AT SUB PANEL 5) REMOVE BOND JUMPER AT SUB PANEL 6) LABEL BREAKERS SUB PANEL 7) SERVICE HAS BEEN ENERGIZED WITHOUT CLEARANCE |
|
| 07/08/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) LOCKED NO ACCESS 2) SERVICE APPEARS TO BE ENERGIZED WITHOUT CLEARANCE |