Permit: T10EL01643

Parcel: 138201090


Addresses:

7042 S LEARY DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/21/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) A PERMIT WILL BE NEEDED IN FUTURE FOR A/C
07/15/2010 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
07/12/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) IDENTIFY ON UNINSULATED NEUTRAL
2) GENERAL LABELING NOT ALLOWED 408.4
3) PLEASE VERIFY PERMIT FOR NEW A/C UNIT
4) SEPERATE GROUNDS AND NEUTRAL AT SUB PANEL
5) REMOVE BOND JUMPER AT SUB PANEL
6) LABEL BREAKERS SUB PANEL
7) SERVICE HAS BEEN ENERGIZED WITHOUT CLEARANCE
07/08/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
There is no access to the site.| 920*
1) LOCKED NO ACCESS
2) SERVICE APPEARS TO BE ENERGIZED WITHOUT CLEARANCE