Permit: T10EL01638

Parcel: 138060500


Addresses:

958 W CALLE ANTONIA

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/24/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/17/2010 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) NEED LISTED BRACE KIT FOR RISER
2) GROUND JUNCTION BOX INSIDE-NOTE CIRCUITS ON INTERIOR ARE NON GROUNDED
3) FINISH #3 PREVIOUS INSPECTION
07/07/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE CONDUCTORS OVER DRIVE TO BE 12' PER 230.24
2) SEAL UNUSED OPENING WITH A NON COMBUSTIBEL PRODUCT
3) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
4) NEED ELECTRICIAN PRESENT TO VERIFY NEW NM CABLE CONNECTIONS
5) PLEASE VERIFY GAS AND WATER BONDS