Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10EL01625
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) NO WORK PROGRESS 2) PLEASE PAY REFEE BEFORE NEXT INSPECTION |
|
07/21/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSED CONDUCTORS TO COMBUSTIBLES BEHIND JUNCTION BOX 2) SECURE CABLE TO JUNCTION BOX 312.5 3) FINISH #3,4 & 5 PREVIOUS |
|
07/07/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ADDRESS ON BLDG AND PERMANENT LABEL ON PANEL 2) CANNOT USED OLD PANEL AS JUNCTION BOX-NEED APPROVED BOX LISTED FOR USE-USE APPROVED CONNECTORS AND TIGHTEN LOCK NUTS 3) CORRECTLY COLOR CONDUCTOR UNINSULATED GROUNDED CONDUCTOR 4) BOND ENCLOSURE 5) PROTECT CONDUCTORS AT FITTINGS 300.4 6) USE APPROVED SIZED SPLICES FOR CONDUCTORS SIZING 7) PANEL LABELING NOT CLEAR AND LEDGIBLE 408.4 8) TIGHTEN ALL LOOSE FITTINGS 9) MESSAGE WAS UNCLEAR COULD NOT UNDERSTAND |
|
07/02/2010 | ELECTRIC - FINAL | Partial Approval |