Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/02/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BRACING ON RISER HAS TO BE LISTED NOT SMASHED EMT 2) GROUND ELECTRODE HAS TO BE STRAPPED TO WALL 3) SERVICE WIRES HAS TO SAY SUN RESISTANT |