Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/21/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ITEMS NOTED AT PANEL CORRECT IDENTIFICATION OF UNGROUNDED CONDUCTOR, MANUFACTURES BREAKERS, ONLY ONE CONDUCTOR TO LUG, ANTI OXIDE COMPOUND AND VERIFY METER BASE AMPACITY 2) FINISH ITEMS 3 & 6 3) MEET WITH ALBERT VARGAS, ROCK OF ROCKY'S ELECTRIC, JASON JAWORSKY AND MY SELF |
|
| 07/20/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* CANCELED BY ALBERT VARGAS FOR LACK OF COMPLETION OF WORK NOTED ON 7/19/2010 |
|
| 07/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH #3, 6 & 14 |
|
| 07/07/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSED NM CABLE AND OPEN SPLICES-FRONT PORCH, ALSO NM CALBES TO LIGHT NOT PER CODE 2) EXPSOED CONDUCTORS IN CEILING, MISSING BOXES AND LIGHT FIXTURES 3) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS 4) MISSING SMOKE DETECTORS BEDROOMS-INSTALL PER INSTRUCTIONS 5) MISSING COVER PLATES 6) RE-INSTALL FURNACE RECEPT 7) CORD HAS ILLEGAL SPLICES 8) PROTECT BULB IN CLOSET 9) KITCHEN RECEPTS TO BE GFCI PROTECTED 10) OPEN WIRING TO DEVICE IN KITCHEN 11) CORD CANNOT PASS THRU CUPBOARDS 12) PLEASE VERIFY WATER HEATER PERMIT 13) BACK PORCH WIRING NOT TO CODE 14) PANEL NOT ? CODE 15) VERIFY PERMITS FOR ADDITION AND GARAGE 16) OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN 17) COMPLETE HANDOUT AND ITEMS LISTED BEFORE RECALL, A REFEE MAY BE ASSESED |
|
| 06/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) LOCKED-NO ACCESS 2) PLEASE READ HANDOUT SHEET ISSUED WITH PERMIT AND COMPLETE 100 PERCENT BEFORE CALLING FOR NEXT INSPECTION |