Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE COPY OF FIRE DAMAGE REPORT FORM DEPT. OF NEIGHBORHOOD RESOURCES 2) KITCHEN COUNTER RECEPTS TO BE GFI PROTECTED 3) INSTALL MISSING WALL PLATES 4) INSTALL WIRE FOR DISHWASHER IN BOX, SAME FOR RANGE 5) RE-SECURE DOOR BELL XFMR TO JUNCTION BOX 6) HAVE GROUNDING TYPE RECEPTS ON UNDERGROUND SYSTEM 7) PROPERLY ENTER WIRES INTO PANEL IN ENTRY CLOSET SEAL OPENING 8) INSTALL SMOKE DETECTORS PER HAND OUT 9) POOL EQUIPMENT REMOVED AND HAS UNSAFE WIRING 10) HAVE DBL TAP AT SERVICE DISCONNECT 11) ALL OUTDOOR RECEPTS TO BE GFI AND HAVE WEATHER PROOF COVERS 12) MISSING FURNACE, NEED TO OBTAIN PERMIT FOR INSTALLING NEW FURNACE 13) SERVICE NEEDS TO BE REPLACED |