Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OPEN JUNCTION BOX ON CEILING CARPORT 2) NEED RECEPT FOR IN WALL A/C UNIT-CANNOT USE EXTENSION CORD WIRING 3) KITCHEN RECEPTS TO BE GFCI PROTECTED 4) BATHROOM RECEPTS TO BE GFCI PROTECTED 5) INSTALL SMOKE DETECTORS IN BEDROOMS AND HALL PER INSTRUCTIONS 6) MISSING LIGHT FURNACE ROOM 7) MISSING COVER PLATES 8) SERVICE METER NOT ATTACHED TO STRUCTURE AND CONDUCTOR NOT INSTALLED TO PANEL 9) A SEPERATE UPGRADE PERMIT WILL BE NEEDED FOR NEW PANEL 10) OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN 11) PLEASE VERIFY PERMIT FOR NEW A/C UNIT |