Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2010 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 07/08/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK 200 AMP SERVICE (NEW)-OK TO CLEAR INCREASE 2) CONTRACTOR OR OWNER TO ADDRESS OTHER CODE VIOLATIONS THRU-OUT STRUCTURES 3) GROUNDED RECEPTS ON UNDERGROUNDED CIRCUITS 4) OVER CROWDED EXISTING FUSE BOXES 5) EXISTING SERVICE IN VIOLATION OF WORKING CLEARANCE 6) DISCUSSED PERMIT WITH LEE RAY-OK TO USE THIS PERMIT FOR MINOR ELECTRICAL REPAIR/UPGRADES |
|
| 06/25/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) SERVICE UPGRADE WITHOUT PERMIT AND INSPECTIONS 2) CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP SERVICE 3) SERVICE NEEDS MAIN 3) NEED PROPER WORKING CLEARANCES 4) SERVICE RACEWAYS NOT BONDED PROPERLY 5) MULTI SERVICES HIRED TO MAKE CORRECTIONS TO ILLEGALLY INSTALLED SERVICE |