Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) CLEARANCE GIVEN UNDER PERMIT #T10EL00664 2) RECALL ACTIVITY #T10EL00664 TO FINISH |
|
| 07/08/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE CLEAN SURFACE UNDER GAS BOND OF PAINT FOR AN EFFECTIVE GROUND FAULT PATH 2) VERIFY IF SPLIT BOLT IS FOR COPPER AND ALUMINUM AND HAVE DISSIMILAR MEAL CONTACT |
|
| 07/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND RISER COMING UP TO BOTTOM OF PANEL 250.92 B & B4 2) ON GROUND BAR CLEAN OFF PANEL BEFORE INSTALLATION OF 250.12 PAINT |