Permit: T10EL01511

Parcel: 14025088A

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/30/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #3 & 4 PREVIOUS INSPECTION
06/28/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REAR COOLER WIRING NOT TO CODE
2) EXCESS PAINT IN DEVICES
3) INSTALL PROPER MAIN BREAKER IN TRAILER PANEL AND WILL NEED MANUFACTURES HOLDOWN
4) FILL UNUSED OPENING IN PANEL
5) NON METALIC FLEX NOT INSTALLED TO CODE
6) FLEXABILITY NEEDED FOR CONDUIT INTO TRAILER
7) CONDUCTORS NOT SIZED PER MAIN BREAKER