Permit: T10EL01504

Parcel: 119042060


Addresses:

3626 S LIBERTY AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/23/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SMOKE DETECTORS NEEDED IN BEDROOMS-INSTALL PER INSTRUCTIONS
2) MISSING COVER PLATES
3) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS, ALSO NEED ARC SHIELDS
4) KITCHEN RECEPTS TO BE GFCI PROTECTED
5) SUPPORT CONDUIT BELOW PANEL
6) MISSING DEAD FRONT
7) ONLY ONE GROUNDED CONDUCTOR TO A TERMINATION
8) BACK FED MAIN TO HAVE MANUFACTURERS HOLDOWN CLAMP AND ONLY ONE CONDUCTOR TO LUGS
9) NM CABLE TO SERVIE TO BE IN METALIC RACEWAY
10) RE-ATTACH WATER BOND AND VERIFY GAS BOND
11) SUPPORT LAUNDRY PORCH RACEWAYS AND PROVIDE WEATHER PROOF COVERS PER 406.8
12) MAINTAIN FLUE SEPERATION FROM COMBUSTIBLES-1"
13) OUTDOOR FIXTURES TO BE FOR WET LOCATION
14) PLEASE VERIFY HEATING UNIT AND ASSOCIATED PERMITS