Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SMOKE DETECTORS NEEDED IN BEDROOMS-INSTALL PER INSTRUCTIONS 2) MISSING COVER PLATES 3) GROUNDED RECEPTS ON NON GROUNDED CIRCUITS, ALSO NEED ARC SHIELDS 4) KITCHEN RECEPTS TO BE GFCI PROTECTED 5) SUPPORT CONDUIT BELOW PANEL 6) MISSING DEAD FRONT 7) ONLY ONE GROUNDED CONDUCTOR TO A TERMINATION 8) BACK FED MAIN TO HAVE MANUFACTURERS HOLDOWN CLAMP AND ONLY ONE CONDUCTOR TO LUGS 9) NM CABLE TO SERVIE TO BE IN METALIC RACEWAY 10) RE-ATTACH WATER BOND AND VERIFY GAS BOND 11) SUPPORT LAUNDRY PORCH RACEWAYS AND PROVIDE WEATHER PROOF COVERS PER 406.8 12) MAINTAIN FLUE SEPERATION FROM COMBUSTIBLES-1" 13) OUTDOOR FIXTURES TO BE FOR WET LOCATION 14) PLEASE VERIFY HEATING UNIT AND ASSOCIATED PERMITS |