Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/25/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OLD DISCONNECT IN DETERIORATED CONDITION-NEED JUNCTION BOX 2) SUPPORT CONDUIT ON SIDE OF PANEL 3) PROVIDE GROUNDING EQUIPMENT CONDUCTOR IN NON METALIC RACEWAYS 4) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 5) BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 6) EQUIPMENT GROUND FOR A/C TO BE 250.122 |