Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) #T10ME00463 NEEDS TO BE FINALED FIRST |
|
| 07/26/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED PERMIT FOR INSTALL OF NEW HEATER OR INCLUDE IN THIS PERMIT 2) ITEM 4 AND 10 LEFT |
|
| 06/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT CONDUITS AT SIDE OF PANEL 2) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH AN APPROVED DEVICE 3) FILL UN-USED OPENINGS IN PANEL AND MISSING DEAD FRONT 4) INSTALL SMOKE DETECTORS ARE PER INSTRUCTIONS 5) SUPPORT CONDUIT IN KITCHEN AND BEDROOM 6) SECURE RANGE BOX TO STRUCTURE 7) INSTALL RECEPTS BACK INTO BOXES AND NEED PLATES 8) SUPPORT CONDUITS ACROSS ROOF 9) NEED WEATHER PROOF COVERS-BACK PORCH 10) NO UNIT FOR HEAT |