Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ISOLATION ON SPLIT BOLTS TO BE EQUAL TO CONDUCTOR 2) FINISH #6 & 8 |
|
| 08/23/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOX TO BE OUTDOOR RATED NEMA 3R 2) CANNOT USE SHEET METAL THREADED SCREWS FOR GROUNDING 250.8 3) CLEAN SURFACE UNDER LUG 250.12 4) INSTALL ALL STRANDS UNDER TERMINATION LUG 5) USE APPROVED SPLICE CONNECTOR ALUMINUM TO COPPER 6) NEUTRAL JUMPER TO BE SIZED TO 200 AMP OR CARRY NEUTRAL BACK TO PANEL 7) #8 + LARGER THRU RACEWAY TO BE ? 300.3 8) VERIFY DERATING PER 310.15 9) USE APPROVED FITTINF FOR LB AND COVER TO BE ACCESSIBLE |
|
| 07/22/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NO LOAD CONNECTED-RECALL AFTER CROSS OVER |