Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T10EL01448
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2010 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
06/18/2010 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFI'S IN KITCHEN ABOVE COUNTER AND SECURE OUTLET TO REFRIDGERATOR 2) COVER UP WIRES IN UTILITY ROOM AND OUTLET HAS COVER PLATE MISSING 3) BEDROOM PHONE PLATES MISSING AND OUTLET BROKEN-REPLACE 4) FURNACE ROOM HAS EXPOSED WIRES AND SPLICES 5) STORAGE ROOM LIGHT MISSING SCREWS AND LIGHT BOX MISSING COVER 6) PANEL MISSING DEAD FRONT AND PANEL SCHEDULE 7) OUTLET BEHIND HOUSE MISSING AND WEATHERPROOF COVER 8) POOL LIGHTS ON HOUSE TO BE REPAIRED |